- Product description
-
Product description
Surge arrester, type 2
• For surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)
• Discharge capacity to 40 kA (8/20) per pole through high-performance varistors
• Modular connectable arrester with cut-off unit and visual status display
• Locking mechanism with vibration protection and voltage keying
• Plastic to UL 94 V-0
• The remote signalling variants (FS) have a potential-free changeover contact for remote signalling
Application: Equipotential bonding in main and sub-distributions.
- Technical data
-
Technical data
Approvals VDE Blow-out no Conductor cross-section, flexible (fine-wire), max. 35 mm² Conductor cross-section, flexible (fine-wire), max. 2 AWG Conductor cross-section, flexible (fine-wire), min. 16 AWG Conductor cross-section, flexible (fine-wire), min. 1,5 mm² Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm² Conductor cross-section, rigid (single-wire/multiwire), max. 2 AWG Conductor cross-section, rigid (single-wire/multiwire), min. 1,5 mm² Conductor cross-section, rigid (single-wire/multiwire), min. 16 AWG Connection cross-section, FM terminals, max. 16 AWG Connection cross-section, FM terminals, max. 1,5 mm² Connection cross-section, FM terminals, min. 21 AWG Connection cross-section, FM terminals, min. 0,5 mm² Dimension 280V Housing material surge protection components PA UL 94 V-0 Installation type DIN rail 35 mm Integrated back-up fuse no Max. mains-side overcurrent protection 160 A gL/gG Maximum back-up fuse 160 A Maximum discharge current (8/20 μs) 40 kA Maximum discharge current (8/20 μs) [L-N] 40 kA Maximum discharge current (8/20 μs) [N-PE] 60 kA Minimum distance 1,5 mm Network form Other Nominal discharge current (8/20 µs) 20 kA Nominal discharge current (8/20 µs) [L-N] 20 kA Nominal discharge current (8/20 µs) [N-PE] 40 kA Operating temperature, max. 80 °C Operating temperature, min. -40 °C Protection rating IP20 Remote signalling no Short-circuit resistance for max. mains-side overcurrent protection 50 kA eff Short-circuit resistant yes Signalling on device Visual SPD to EN 61643-11 Type 2 SPD to IEC 61643-1 Class II SPD to UL 1449 Type 4 Switching power AC 230 V; 0,5 A Switching power DC 230 V; 0,1 A / 75 V; 0,5 A Test class, type 2 yes Torque 4 Nm - All types
- Downloads
-
Data sheet V20-LCF-0-280 / 5095524 , 0.24MB , pdfMounting instructions Surge Controller V20-LCF...280 , 3.10MB , pdf
Serbia - English